XF Series Cyclone Dust Catcher
|
|
|
|
|
|
|
|
Purpose
It is used inCity Gates Stations,gas stations for filtrating gas and eliminating gas impurity.
Applicable medium
Natural gas, Manufactured gas, Liquefied petroleum gas,and other gases.
Technical Parameters
Design Pressure:1.6MPa、2.5 MPa、4.0 MPa、6.4 MPa
Work Pressure:1.0MPa、1.6 MPa、2.5 MPa、4.0 MPa
Filtration Efficiency:≥90%
Temperature Capabilities:normal temperature
Calibre Dimensions: DN65、DN100、DN125、DN150、DN200、DN250
Type
XF-65-XF-150: hand hole operation,a leglike support
XF-200-XF-250:people hole operation,normal support
Selected Equipments
Pressure Difference Meter
Flange Cover Open Equipmen
Safety Valve
Dirt
Clean Valve
Dimension(Design Pressure≤2.5MPa)
MODEL |
Inlet and Outlet
mm
|
DN×H
mm
|
h
mm
|
Emission size e
mm
|
Db
mm
|
XF-65 |
DN65
|
300×1700 |
1400 |
DN50
|
Φ282 |
XF-100 |
DN100 |
600×2500 |
2130 |
DN65 |
Φ583 |
XF-125 |
DN125 |
700×3000 |
2580 |
DN80 |
Φ689 |
XF-150 |
DN150 |
800×3300 |
2850 |
DN80 |
Φ792 |
XF-200 |
DN200 |
1200×3930 |
3350 |
DN100 |
Φ840 |
XF-250 |
DN250 |
1400×4330 |
3700 |
DN100 |
Φ1050 |
|
|
|